Diesel, Petrol & Gas Fueled Engine Rooms 柴油、汽油與天然氣發電機房

Generator rooms can be found in many industrial onshore applications as part of the production process or for backup or emergency purposes. Flaming fires are to be expected. Possible equipment and production loss because of unscheduled shutdowns
發電機房應用於許多工業上,作為生產過程的一部份或用於 備用或緊急需求。具起火的風險性,可能會造停工、設備 與生產損失

Typical Risks 標準風險

  1. Hot surfaces of the engine and the exhaust system may ignite Fuel or Lubricants
    發電機與排氣系統的高溫表面可能會點燃燃油或潤滑油

  2. Hot surfaces, (Blackbody Radiation), may act as a Spurious alarm source
    高溫表面(黑體輻射)可能會造假警報

Typical Considerations 標準注意事項

  1. Shadow Effects 視角遮蔽

  2. Correct Flame Detector choice. Diesel fumes and mist may be an inhibitor
    選用正確的火焰偵測器,柴油煙霧可作為良好的假警報抑制劑

  3. Intense ventilation in the generator room could effect response time
    發電機房的快速通風會影響反應時間

  4. These are critical systems. Use at least two Flame Detectors, (use at least four Flame Detectors if voting)
    此為重要設備。至少需要使用2個火烙偵測器(4個更為妥當)

Recommendations 推薦使用

  1. IR3

  2. UV/IR (if inhibitors are not present/無柴油煙霧時)